Interlayment shall comply with ASTM D226, Type I. 26 gage [0.019 inch (0.5 mm)] corrosion-resistant sheet metal and shall extend not less than 11 inches (279 mm) from the centerline each way. PDF 2018 IRC UPDATE Handout 9-1-18 - ICC 2018 IRC. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum, Asphalt shingles shall have the minimum number of fasteners required by the manufacturer's, Where required, ice barriers shall comply with, Flashing for asphalt shingles shall comply with this section and the asphalt shingle manufacturer's, Base and cap flashing shall be installed in accordance with manufacturer's instructions. Valley flashing shall be not less than 15 inches (381 mm) wide. Section R803 Roof Sheathing R803.2 Wood Structural Panel Sheathing (Roof Online Note: This subsection covers plywood and OSB sheathing. Above-deck thermal insulation board shall comply with the standards in Table 906.2. Install a two-layer #30 felt underlayment system. Adjacent segments of drip edge shall be overlapped not less than 2 inches (51 mm). Sheathing Requirements R905.2.1 Asphalt shingles shall be fastened to solidly sheathed decks. Mineral-surfaced roll roofing shall not be applied on roof. Materials and methods of application used for recovering or replacing an existing, The structural roof components shall be capable of supporting the, Flashings shall be reconstructed in accordance with, Chapter 9 addresses the design and construction of, R902.2 Fire-Retardant-Treated Shingles and Shakes, R902.3 Building-Integrated Photovoltaic Product, R902.4 Rooftop-Mounted Photovoltaic Panel Systems, R903.4.1 Secondary (Emergency Overflow) Drains or Scuppers, R904.3 Material Specifications and Physical Characteristics, Section R905 Requirements for Roof Coverings, In areas where the average daily temperature in January is 25F (-4C) %%EOF Asphalt shingles shall meet the classification requirements of Table 905.2.4.1 for the appropriate ultimate design wind speed. Foam plastic materials and installation shall comply with. For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall be permitted. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). Slate shingles shall be secured to the roof with two fasteners per slate. Foamed-in-place roof insulation shall be installed in accordance with this chapter and the manufacturer's instructions. Stainless steel fasteners are acceptable for metal roofs. 2018 International Building Code (Ibc) | Icc Digital Codes Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380, Class M. Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer's instructions. For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. SECTION R801 GENERAL. Thermoplastic single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. The ratio changes based on climate severity. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. Flashing and counterflashing shall be made with sheet metal. The installation of asphalt shingles shall comply with the provisions of this section. Asphalt shingles shall be used only on roof. The installation of thermoplastic single-ply roofing shall comply with the provisions of this section. Install flashing at roof penetrations and wall intersections. Liquid-applied roofing shall comply with ASTM C836, C957, D1227, D3468, D6083, D6694 or D6947. Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Roof Sheathing Ring Shank nails have been added to Table R602.3(1) Fastening Schedule with the designation RSRS-01 (2-3/8" x 0.113") as an option for roof sheathing attachment. Spray-applied polyurethane foam insulation shall comply with ASTM C1029, Type III or IV or ASTM D7425. Modified bitumen roofs shall be installed in accordance with this chapter and the manufacturer's instructions. %PDF-1.6 % For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. DEWALT Building Code Reference: Based on the 2018 International Allowable spans for lumber sheathing shall conform to IRC Table R803.1. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 / 8 -inch- diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 / 4 inch (19.1 mm) into the roof sheathing. Slate shingles shall comply with ASTM C406. The installation of wood shingles shall comply with the provisions of this section. In areas where the average daily temperature in January is 25F (-4C) or less, Wood shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Mineral-surfaced roll roofing shall not be applied on roof. Materials and methods of application used for recovering or replacing an existing, The structural roof components shall be capable of supporting the, Flashings shall be reconstructed in accordance with, Chapter 9 addresses the design and construction of, R902.2 Fire-Retardant-Treated Shingles and Shakes, R902.3 Building-Integrated Photovoltaic Product, R902.4 Rooftop-Mounted Photovoltaic Panel Systems, R903.4.1 Secondary (Emergency Overflow) Drains or Scuppers, R904.3 Material Specifications and Physical Characteristics, Section R905 Requirements for Roof Coverings, R905.2.4.1 Wind Resistance of Asphalt Shingles, R905.14 Sprayed Polyurethane Foam Roofing, R905.17 Building-Integrated Photovoltaic (BIPV) Roof Panels Applied Directly to the Roof Deck, Section R907 Rooftop-Mounted Photovoltaic Panel Systems, R907.1 Rooftop-Mounted Photovoltaic Panel Systems, Building-integrated photovoltaic products. R803.1 Lumber sheathing. For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. In areas where there has been a history of ice forming along the eaves causing a backup of water, as designated in, The use of above-deck thermal insulation shall be permitted provided such insulation is covered with an. 12 oz/sq ft for preformed metal shingle systems. 2 RESIDENTIAL ROOFING GUIDE 2018 IRC. Wood shingles shall be laid with a side lap not less than 1, NAIL REQUIREMENTS FOR WOOD SHAKES AND WOOD SHINGLES, Roof flashing shall be not less than No. Where anchored masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and counterflashing shall be provided in accordance with, Flashing against a vertical front wall, as well as soil, A drip edge shall be provided at eaves and rake edges of shingle roofs. Liquid-applied roofing shall be installed in accordance with this chapter and the. arrow_right. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. 0 Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Foamed-in-place roof insulation shall be installed in accordance with this chapter and the manufacturer's instructions. hb```g``:AX,;nkga3l~/ * Asphalt shingle packaging shall bear a. Thermoplastic single-ply membrane roofs shall have a design. Valley linings shall be installed in accordance with the manufacturer's instructions before applying shingles. In areas where there has been a history of ice forming along the eaves causing a backup of water, as designated in, The use of above-deck thermal insulation shall be permitted provided that such insulation is covered with an. Sprayed polyurethane foam roofs shall have a design. 2018 International Residential Code (Irc) | Icc Digital Codes The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D 6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Roof valley flashing shall be not less than No. The installation of liquid-applied roofing shall comply with the provisions of this section. The lecture and activity format allows participants to discuss the changes, reasons for the changes, and answer knowledge review questions. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.5 mm) zinc coated G90. 2018 International Residential Code (Irc) | Icc Digital Codes Terne coating of 40 lb per double base box, field painted where applicable in accordance with, 0.027 inch minimum thickness: 99.995% electrolytic high-, ASTM D6162; D6163; D6164; D6222; D6223; D6298, As an alternative, self-adhering polymer-modified bitumen, As an alternative, a minimum 4-inch-wide (102 mm) strip of self-adhering polymer-modified bitumen membrane complying with ASTM D1970, installed in accordance with the, The cap nail shank shall be not less than 0.083 inch (2.11 mm) for ring shank cap nails and 0.091 inch (2.31 mm) for smooth shank cap nails. Stainless steel fasteners are acceptable for metal roofs. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). Wood shakes shall comply with the requirements of Table 905.8.5. PDF Indiana Register FIRE PREVENTION AND BUILDING SAFETY COMMISSION CEB Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. or less. For SI: 1 ounce per square foot = 0.305 kg/m, The installation of modified bitumen roofing shall comply with the provisions of this section and the manufacturer's, Modified bitumen roofing shall have a design. Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380, Class M. Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer's instructions. Install drip edges at eaves and rakes. Roof valley flashing shall be not less than No. Liquid-applied roofing shall have a design. 2018 International Residential Code (Irc) | Icc Digital Codes Galvanized fasteners shall be used for steel roofs. Self-adhering polymer modified bitumen. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2. Unvented Conditioned Attic with Spray Foam Insulation Below Roof - PNNL Minimum headlap for slate shingles shall be in accordance with Table R905.6.5. Same as Maximum Ultimate Design Wind Speed, Preservative-treated shakes and shingles of, Fire-retardant-treated shakes and shingles of, Preservative-treated tapersawn shakes of Southern pine treated in accordance with AWPA Standard U1 (Commodity Specification A, Special Requirement 4.6), Forest Products Laboratory of the Texas Forest Services, Preservative-treated tapersawn shakes of Southern Yellow Pine, Asphalt-saturated and asphalt-coated organic felt base sheet, Asphalt-saturated organic felt (perforated), Coal-tar primer used in roofing, dampproofing and waterproofing, ASTM B370 minimum 16 oz/sq ft and 12 oz/sq ft high-yield copper for metal-sheet. Thermoset single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs. Wood shingles shall be laid with a side lap not less than 1, NAIL REQUIREMENTS FOR WOOD SHAKES AND WOOD SHINGLES, Roof flashing shall be not less than No. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. The installation of asphalt shingles shall comply with the provisions of this section. Rooftop-mounted photovoltaic systems shall be installed in accordance with the manufacturer's instructions. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. IRC Section Table 301.5 Minimum Uniformly Distributed Live Loads: SECTION R802 WOOD ROOF FRAMING. Wood shakes shall be installed in accordance with this chapter and the, The starter course at the eaves shall be doubled and the bottom layer shall be either 15-inch (381 mm), 18-inch (457 mm) or 24-inch (610 mm) wood shakes or wood shingles.